Group 6:  Protection Parameters 
6-00 
Over-Voltage Stall Prevention 
 
 
 
 
Factory Setting: d1
 Settings 
d0 
Disable 
  
d1 
Enable 
 
During deceleration, the motor DC bus voltage may exceed its Maximum Allowable Value due 
to motor regeneration. When this function is enabled, the AC drive will stop decelerating. 
Maintaining a constant output frequency when it happens. The AC drive will only resume 
deceleration when the voltage drops below preset value. 
NOTE
  
With a moderate inertial load, the over-voltage during deceleration won’t happen, and the drive will 
stop in programmed time. The AC drive will automatically extend the deceleration time with high 
inertial loads.  If deceleration time is critical for the application, then dynamic brake resistors should 
be used. 
 
6-01 
Over-Voltage Stall Prevention Level 
Unit: 1
 
Settings  230V Series  d350 to d410V 
Factory Setting: 390
 
 
460V Series d700 to d820V 
Factory Setting: 780 
 
During deceleration, the DC bus voltage may exceed its maximum allowable value due to 
motor regeneration. When this function is enabled, the AC drive will stop decelerating. 
Maintaining a constant output frequency when it happens. The AC drive will resume 
deceleration when the voltage drops below preset value. 
 
With a moderate inertial load, the over-voltage during deceleration won’t happen, and the 
drive will stop in programmed time. The AC drive will automatically extend the deceleration 
time with high inertial loads. If deceleration time is critical for the application, then dynamic 
brake resistors should be used.