Chapter 5 Parameters|VFD-S Series 
Revision August 2008, SE09, SW V2.61 
5-57
 
Group 7:  Motor Parameters 
7-00 
Motor Rated Current 
Unit: 1
 
Settings 
d30 to d120% 
Factory Setting: d85
 
This parameter will limit the AC drive output current in order to prevent the motor from 
overheating. 
 
7-01 
Motor No-load Current 
Unit: 1
 
Settings 
d0 to d90% 
Factory Setting: d50
 
The rated current of the AC drive is regarded as 100%.  Motor setting of no-load current will 
effect the slip compensation.  The setting value must be less than motor rated current setting 
Pr.7-00 
 
7-02 
Torque Compensation 
Unit: 0.1
 
Settings 
d0 to d10 
Factory Setting: d1
 
This parameter may be set so that the AC drive will increase its voltage output during start-up 
to obtain a higher initial starting torque. 
 
7-03 
Slip Compensation 
Unit: 0.01
 
Settings 
d0.0 to d10.0 
Factory Setting: d0.0
 
While driving an asynchronous motor, load on the AC drive will increase, causing an increase 
in slip. This parameter may be used to compensate the nominal slip within a range of 0 to 10. 
When the output current of the AC drive is greater than the motor no-load current (Pr.7-01), 
the AC drive will adjust its output frequency according to this parameter.