Chapter 5 Parameters|VFD-S Series 
Revision August 2008, SE09, SW V2.61 
5-59
 
 
DC Brake during Start-up is used for loads that may move before AC drive starts, such as 
fans and pumps. These loads may also be moving in the wrong direction.  Under such 
circumstances, DC Brake can be executed to hold the load in position before applying a 
forward motion. 
 
DC Brake during stopping is used to decrease stopping time and also to hold a stopped load 
in position.  For high inertial loads, a dynamic brake resistor may be needed for quick 
decelerations. 
 
8-04 
Momentary Power Loss Operation Selection 
 
 
 
Factory Setting: d0
 Settings 
d0 
Operation 
stops after momentary power loss 
 
 
d1 
Operation continues after momentary power loss, speed search 
starts with the Master Frequency reference value 
 
 
d2 
Operation continues after momentary power loss, speed search 
starts with the minimum frequency 
 
8-05 
Maximum Allowable Power Loss Time 
Unit: 0.1
 
Settings 
d0.3 to d5.0Sec 
Factory Setting: d2.0
 
During a power loss, if the power loss time is less than the time defined by this parameter, the 
AC drive will resume operation.  If the Maximum Allowable Power Loss Time is exceeded, the 
AC drive output is then turned off. 
 
8-06 
Base Block Speed Search 
Unit: 0.1 
 
Settings 
d0.3 to d5.0Sec 
Factory Setting: d0.5
 
When a momentary power loss is detected, the AC drive turns off for a specified time interval 
determined by Pr.8-06 before resuming operation.  This time interval is called Base-Block.  
This parameter should be set to a value where the residual output voltage is nearly zero, 
before the drive resumes operation. 
 
This parameter also determines the searching time when performing external Base-Block and 
fault reset. 
 
8-07 
Current Limit for Speed Search 
Unit: 1
 Settings 
d30 to d200
% 
Factory Setting: d150