Chapter 5 Parameters|VFD-S Series 
5-6
 
Revision August 2008, SE09, SW V2.61
 
Pr. Explanation 
Settings 
Factory 
Setting
NOTE
4-04 
Multi-Function Input Terminal 1 (M0, 
M1)  
d0: No Function 
d1: FWD/STOP, REV/STOP 
d2: FWD/REV, RUN/STOP 
d3: 3-wire Operation Control Mode
d4: E.F. External Fault Input (N.O.)
d5: E.F. External Fault Input (N.C.)
d6: Reset 
d7: Multi-Step Speed Command 1 
d8: Multi-Step Speed Command 2 
d9: Multi-Step Speed Command 3 
d1 
 
4-05  Multi-Function Input Terminal 2 (M2) 
d10: Jog Operation 
d11: Accel/decel Inhibit 
d6 
 
4-06  Multi-Function Input Terminal 3 (M3) 
d12: First or Second 
Acceleration/deceleration Time 
Selection 
d13: External base block (N.O.) 
d14: External base block (N.C.) 
d7 
 
4-07  Multi-Function Input Terminal 4 (M4) 
d15: Up: Increment master 
frequency 
d16: Down: Decrement master 
frequency 
d17: Run PLC Program 
d8 
 
4-08  Multi-Function Input Terminal 5 (M5) 
d18: Pause PLC Program 
d19: Counter Trigger Signal 
d20: Counter Reset 
d21: Select ACI / Deselect AVI 
d22: PID Function Disabled 
d23: JOG FWD 
d24: JOG REV 
d25: The source of master 
frequency is AVI. 
d26: The source of master 
frequency is ACI. 
d27: Press UP/DOWN key to switch 
forward/reverse (N.O.) motion
d28: Press UP/DOWN key to switch 
forward/reverse (N.C.) motion
d29: M0:  0: RUN 1: STOP, M1: no 
function, Direction is controlled 
by keypad 
d9 
 
4-09  Line Start Lockout 
d0: Disable 
d1: Enable 
d0 
 
4-10 Up/Down 
Mode 
d0: Based on accel/decel time 
d1: Up frequency according to 
constant speed, down frequency 
according to deceleration time 
d2: Up frequency according to 
acceleration time, down 
frequenc according to constant 
speed 
d3: Constant speed 
d3 
 
4-11 
Accel/Decel Rate of Change of 
UP/DOWN Operation with Constant 
Speed 
0~1000, unit: 5 Hz/sec 
d1