Chapter 5 Parameters|VFD-S Series 
5-8
 
Revision August 2008, SE09, SW V2.61
 
Pr. Explanation 
Settings 
Factory 
Setting
NOTE
d4: Enabled during running. After 
the over-torque is detected, stop 
running. 
6-04  Over-Torque Detection Level 
d30 to d200% 
d150
 
6-05  Over-Torque Detection Time 
d0.1 to d10.0 Sec 
d0.1
 
6-06 
Electronic Thermal Overload Relay 
Selection 
d0 to d2 
d2 
 
6-07 
Electronic Thermal 
Characteristic 
d30 to d600 Sec 
d60 
 
d0: No fault 
d1: Over current (oc) 
d2: Over voltage (ov) 
d3: Over heat (oH) 
6-08  Present Fault Record 
d4: Over load (oL) 
d5: Over load (oL1) 
d6: External fault (EF) 
6-09  Second Most Recent Fault Record 
d7: Reserved 
d8: Reserved 
d9: Excess current during 
acceleration (ocA) 
d10: Excess current during 
deceleration (ocd) 
d11: Excess current during steady 
state (ocn) 
6-10   Third Most Recent Fault Record 
d12: Ground fault (GF) 
d0 
 
  
d13: 
Reserved 
 
 
 
 
d14: Low voltage (Lv) 
 
 
 
 
d15: CPU failure 1 (cF1) 
 
 
 
 
d16: CPU failure 2 (cF2) 
 
 
 
 
d17: Base block (b.b.) 
 
 
 
 
d18: Overload (oL2) 
 
 
 
 
d19: Auto acceleration/deceleration 
failure (cFA) 
 
 
 
 
d20: Software protection enable 
(codE) 
 
 
  
d21: 
Reserved 
 
 
 
 
d22: CPU failure (cF3.1) 
 
 
 
 
d23: CPU failure (cF3.2) 
 
 
 
 
d24: CPU failure (cF3.3) 
 
 
 
 
d25: CPU failure (cF3.4) 
 
 
 
 
d26: CPU failure (cF3.5) 
 
 
 
 
d27: CPU failure (cF3.6) 
 
 
 
 
d28: CPU failure (cF3.7) 
 
 
 
 
d29: Hardware protection failure 
(HPF.1) 
 
 
 
 
d30: Hardware protection failure 
(HPF.2) 
 
 
 
 
d31: Hardware protection failure 
(HPF.3) 
 
 
 
 
d32: Communication time-out 
(CE10) 
 
 
  
d33: 
Reserved 
 
 
 
 
d34: Software error (SErr)