Chapter 4 Parameters| 
4-2
 
Revision August 2008, 03VE, SW V2.04
 
4.1 Summary of Parameter Settings 
: The parameter can be set during operation.  
Group 0 System Parameters 
Pr. 
Explanation 
Settings 
Factory 
Setting
VF  VFPG  SVC  FOCPG  TQRPG 
00-00 
Identity Code of the AC 
motor drive 
Read-only
 
 
 
00-01 
Rated Current Display of 
the AC motor drive 
Read-only 0 
 
 
00-02 
Parameter Reset 
0: No function 
1: Read only 
2: Enable group 11 parameters setting 
8: Keypad lock 
9: All parameters are reset to factory settings (50Hz, 
220V/380V)  
10: All parameters are reset to factory settings (60Hz, 
220V/440V) 
 
 
00-03  Start-up Display Selection 
0: Display the frequency command value (LED F) 
1: Display the actual output frequency (LED H) 
2: Multifunction display, see Pr.00-04 (LED U) 
3: Display the output current (A) 
 
 
00-04 
Content of Multi Function 
Display 
0: Display output current (A) 
1: Display counter value (C) 
2: Display output frequency (H) 
3: Display DC-BUS voltage (
u
4: Display output voltage (E)  
5: Output power factor angle (n) 
6: Display output power (kW) 
7: Display actual motor speed (HU)  
8: Display estimate output torque (kg-m) 
9: Display PG position (G) (refer to Pr.10-00 and Pr.10-
01) 
10: Display PID feedback 
11: Display AVI (%) 
12: Display ACI (%) 
13: Display AUI (%) 
14: Display the temperature of heat sink (°C) 
15: Display the temperature of IGBT (°C) 
16: The status of digital input (ON/OFF) 
17: The status of digital output (ON/OFF) 
18: Multi-step speed 
19: The corresponding CPU pin status of digital input 
20: The corresponding CPU pin status of digital output 
21: Number of actual motor revolution (PG1 of PG card) 
22: Pulse input frequency (PG2 of PG card) 
23: Pulse input position (PG2 of PG card) 
 
 
00-05  User-Defined Coefficient K 
Digit 4: decimal point number (0 to 3) 
Digit 0-3: 40 to 9999 
 
 
00-06 Software 
Version 
Read-only 
#.# 
 
 
00-07  Password Input 
1 to 9998 and 10000 to 65535 
0 to 2: times of wrong password 
 
 
00-08  Password Set 
1 to 9998 and 10000 to 65535 
0: No password set or successful input in Pr.00-07 
1: Password has been set 
 
 
00-09  Energy Saving Gain 
10~1000 % 
100%
 
 
 
 
00-10 
Control Method 
0: V/f Control 
1: V/f Control + Encoder (VFPG) 
2: Sensorless vector control (SVC) 
3: FOC vector control + Encoder  (FOCPG) 
4: Torque control + Encoder (TQRPG) 
 
 
00-11 
V/f Curve Selection 
0: V/f curve determined by group 01 
1: 1.5 power curve 
2: Square curve 
 
 
 
00-12 
Constant/Variable Torque 
Selection 
0: Constant Torque (100%) 
1: Variable Torque (125%) 
 
 
 
00-13 
Optimal 
Acceleration/Deceleration 
Setting 
0: Linear accel./decel. I 
1: Auto accel., linear decel. 
2: Linear accel., auto decel. 
3: Auto accel./decel.