2-18
Cisco 7500 Series Installation and Configuration Guide
OL-5008-03 B0
Chapter 2      Preparing for Installation
  Equipment Rack-Mounting Guidelines
If you plan to use an equipment shelf, ensure that the shelf is constructed to support the weight and 
dimensions of the chassis.  
 shows the chassis footprint, which you will need if you are 
designing a customized shelf. 
If you use 2-post racks, be sure that the rack is bolted to the floor and secured. One end of the chassis 
mounts to the two rack posts with the chassis ears, and the rest of the chassis is cantilevered off the 
posts. Ensure that the weight of the chassis does not make the rack unstable. Some 2-post racks are 
also secured to ceiling brackets if warranted by the weight of the equipment in the rack. 
In addition to the preceding guidelines, we recommend you review the precautions for avoiding 
overtemperature conditions in the 
.
Cisco 7507 and Cisco 7507-MX Rack-Mount Considerations
An optional rack-mounting kit is available for mounting the Cisco 7507 or Cisco 7507-MX in a standard 
19-inch (48.26 cm) equipment rack. The mounting kit is not suitable for use with 2-post equipment 
racks, or those with obstructions (such as a power strip) that could impair access to the interface 
processors and power supplies. In telco environments or at installation sites that use nonstandard racks, 
the router can be mounted on an equipment shelf, provided that the rack dimensions allow safe 
installation and access to the power supplies and interface processors.  
 shows the chassis 
footprint and outer dimensions.
To use the optional rack-mount kit, your equipment rack must meet the following requirements:
The width of the rack, between the two front mounting strips or rails, must be 17.75 inches (45.09 
cm).
The depth of the rack, between the front and rear mounting strips, must be at least 19.25 inches 
(48.90 cm) but not more than 32 inches (81.28 cm).
The height of the chassis is approximately 20 inches (50.08 cm) (19.25 inches [48.90 cm] when the 
chassis feet are removed). The rack must have sufficient vertical clearance to insert the chassis and, 
if required after installation, to remove the chassis feet. 
If the rack has a vertical power strip or other potential obstacle, ensure that it will allow sufficient 
clearance to install and remove both interface processors (11 inches [27.94 cm] deep) and power 
supplies (16 inches [40.64 cm] deep), both of which must be pulled straight out of the chassis.