Cisco Systems Cisco CRS-1 Manual De Usuario

Descargar
Página de 146
   
2-7
Cisco CRS-1 Carrier Routing System 4-Slot Line Card Chassis Installation Guide
OL-10971-07
Chapter 2      Installing and Removing Power Components
DC Power Systems on the Cisco CRS-1 4-Slot Router
DC Power Shelf Guidelines
At sites where the Cisco CRS-1 4-slot line card chassis is equipped with a DC power input shelf and 
power supplies, observe the following guidelines: 
  •
All power connection wiring should follow the rules and regulations in the National Electrical Code 
(NEC) and any local codes.
  •
Each DC-input power entry module connection is rated at 60-A maximum. A dedicated, 
commensurately rated DC power source is required for each power supply connection.
  •
Each power supply requires one -48 VDC input, or four inputs for each power shelf (in which each 
input consists of a pair of positive and negative wires), and one power-shelf grounding wire.
  •
For DC power cables, we recommend that you use commensurately rated, high-strand-count copper 
wire cable. Each DC power supply requires one -48 VDC input, which means that there are two 
wires for each power supply, or eight total wires (four pairs) for each power shelf, plus the grounding 
wire. The length of the wires depends on the router’s location. These wires are not available from 
Cisco Systems; they are available from any commercial vendor. 
  •
DC power cables must be terminated by cable lugs at the power-shelf end. The lugs should be dual 
hole and able to fit over M6 terminal studs at 0.625-in (15.88-mm) centers (for example, Panduit 
part number LCD2-14A-Q or equivalent) (see 
Figure 2-4
DC Power Cable Lug
Color Coding of the Source DC Power Cable
The color coding of the source DC power cable leads depends on the color coding of the site DC power 
source. Typically, green or green and yellow indicates that the cable is a ground cable. Because no color 
code standard exists for the source DC wiring, you must ensure that the power cables are connected to 
the DC-input power shelf terminal studs in the proper positive (+) polarity and negative (–) polarity.
DC Cable Polarity Labels
Sometimes, the source DC cable leads might have a positive (+) or a negative (–) label. This label is a 
relatively safe indication of the polarity, but you must verify the polarity by measuring the voltage 
between the DC cable leads. When making the measurement, the positive (+) lead and the negative (–) 
lead must always match the (+) and (–) labels on the power shelf. 
Caution
The DC-input power supplies contain circuitry to prevent damage due to reverse polarity, but you should 
correct a reverse-polarity condition immediately.
Crimp area
210840
2.40
0.60
0.10
0.25
0.38
0.63
End View
Ø 0.27
2 holes