Sun Microsystems 4500/3 Manual De Usuario
Chapter 2
The Cluster Platform 4500/3 System
15
Power and Heating Requirements
The Cluster Platform 4500/3 hardware should have two dedicated AC breaker
panels. The cabinet should not share these breaker panels with other, unrelated
equipment. The system requires two L30-R receptacles for the cabinet, split between
two isolated circuits. For international installations, the system requires two Blue
32AIEC309 (international) receptacles.
panels. The cabinet should not share these breaker panels with other, unrelated
equipment. The system requires two L30-R receptacles for the cabinet, split between
two isolated circuits. For international installations, the system requires two Blue
32AIEC309 (international) receptacles.
If the cabinet is installed on a raised floor, cool conditioned air should be directed to
the bottom of each rack through perforated panels.
the bottom of each rack through perforated panels.
The 72-inch cabinet in the Cluster Platform 4500/3 consumes power and dissipates
heat, as shown in
heat, as shown in
.
TABLE 2-2
Cluster Platform Rack Components
Component
Quantity
Sun StorEdge expansion cabinet
1
Ethernet hub
1
Netra T1 AC200 management server
1
Netra st D130 boot disks
4
Air baffle
2
Sun Enterprise cluster node
2
Sun StorEdge T3 array
2
Terminal concentrator
1
TABLE 2-3
Power and Heat Requirements for Cluster Platforms
72-Inch Cabinet
Maximum Power Draw
Heat Dissipation
1
10480 W
33786 BTUs/hr.