LFt
Parameter name:
Altivar fault code
Logic address:
7121 = 16#1BD1
Type:
WORD (listing)
CANopen index:
2029/16
Read/write:
R
INTERBUS index:
5FB9/58
Unit:
-
DeviceNet path:
84/01/7A
The last fault that occurred remains stored in the "Altivar fault code" 
(LFt)
 parameter, even if it disappears and even after 
the drive has been turned off and then on again.
0:
(nOF)
No fault
1:
Reserved
2:
[Control Eeprom]
(EEF1)
Internal memory fault, control card
3:
[Incorrect config.]
(CFF)
Option card changed or removed
Control card replaced by a control card configured on a drive with a different rating
The current configuration is inconsistent 
4:
[Invalid config.]
(CFI)
Invalid configuration. The configuration loaded in the drive via the bus or 
communication network is inconsistent
5:
[Modbus com.]
(SLF1)
Interruption in communication on the Modbus bus
6:
[internal com. link]
(ILF)
Communication fault between option card and drive
7:
[Com. network]
(CnF)
Communication fault on communication card
8:
[External flt-LI/Bit]
(EPF1)
Fault triggered by an external device, depending on user
9:
[Overcurrent]
(OCF)
Parameters in 
[SETTINGS]
 
(SEt-)
 and
 [1.4 MOTOR CONTROL]
 
(drC-)
 menus 
are not correct 
Inertia or load too high
Mechanical locking
10:
[Precharge]
(CrF1)
Pre-charge relay control fault or charging resistor damaged
11:
[Speed fdback loss]
(SPF)
Encoder feedback signal missing
12:
Reserved
13:
[AI2 4-20mA loss]
 
(LFF2)
Loss of the 4-20 mA reference on analog input AI2
14:
[PTC1 probe]
(PtF1)
PTC1 probes open or shorted
15:
[PTC1 overheat]
(OtF1)
Overheating of the PTC1 probes detected
16:
[Drive overheat]
(OHF)
Drive temperature too high
17:
[Motor overload]
(OLF)
Triggered by excessive motor current
18:
[Overbraking]
(ObF)
Braking too sudden or driving load
19:
[Mains overvoltage]
(OSF)
Line voltage too high
Disturbed line supply
20:
[1 output phase loss]
(OPF1)
Loss of one phase at drive output
21:
[Input phase loss]
(PHF)
Drive incorrectly supplied or a fuse blown
Loss of one phase
Three-phase ATV61 used on a single-phase line supply
Unbalanced load
This protection only operates with the drive on load
22:
[Undervoltage]
(USF)
Line supply too low
Transient voltage dip
Damaged precharge resistor
23:
[Motor short circuit]
(SCF1)
Short-circuit or grounding at the drive output
Significant earth leakage current at the drive output if several motors are 
connected in parallel
24:
[Overspeed]
(SOF)
Instability or driving load too high
25:
[Auto-tuning]
(tnF)
Special motor or motor whose power is not suitable for the drive
Motor not connected to the drive
26:
[Rating error]
(InF1)
The power card is not the one stored
27:
[Incompatible PB]
(InF2)
The power card is incompatible with the control card
28:
[Internal serial link]
(InF3)
Communication fault between the internal cards
29:
[Internal MFG area]
(InF4)
Internal data inconsistent
30:
[Power
 
EEprom]
(EEF2)
Internal memory fault, power card
31:
[Impedant
 
sh. circuit]
(SCF2)
Impedant short-circuit
32:
[Ground short circuit]
(SCF3)
Ground short-circuit
33:
[3 output phase loss]
(OPF2)
Motor not connected or motor power too low
Output contactor open
Instantaneous instability in the motor current
34:
[CAN
 
com.]
(COF)
Interruption in communication on the CANopen bus
Code