Fault parameters
 
104
CIC
Parameter name:
Incorrect configuration
Logic address:
7130 = 16#1BDA
Type:
WORD (bit register)
CANopen index:
2029/1F
Read/write:
R
INTERBUS index:
5FB6/1A
Unit:
-
DeviceNet path:
84/01/83
bit 0: = 1: Change of rating
bit 1: Reserved (= 0 or 1)
bit 2: = 1: The network card has been removed
bit 3: = 1: Saving to the EEPROM non-volatile memory is inconsistent with power on
bit 4: = 1: The network card has been changed
bit 5: Reserved (= 0 or 1)
bit 6: = 1: The (Controller Inside) card has been removed
bit 7: = 1: The (Controller Inside) card has been changed
bit 8: Reserved (= 0 or 1)
bit 9: = 1: An I/O card has been removed
bit 10: = 1: The I/O card has been changed
bit 11: Reserved (= 0 or 1)
bit 12: = 1: An encoder card has been removed
bit 13: = 1: The encoder card has been changed
bit 14: Reserved (= 0 or 1)
bit 15: Reserved (= 0 or 1)
If one of these events occurs, the drive switches to 
[Incorrect config.] 
(CFF)
 fault mode and then automatically applies a 
factory setting.
APF
Parameter name:
"Controller Inside" card fault code
Logic address:
7133 = 16#1BDD
Type:
UINT
CANopen index:
2029/22
Read/write:
R
INTERBUS index:
5FB0/99
Unit:
1
DeviceNet path:
84/01/86
The fault remains saved in the parameter, even if it disappears.
The parameter is reset after the drive is disconnected and then reconnected.
Consult the "Controller Inside" card manual.
CnF
Parameter name:
Network card fault code
Logic address:
7132 = 16#1BDC
Type:
UINT
CANopen index:
2029/21
Read/write:
R
INTERBUS index:
5FB0/98
Unit:
1
DeviceNet path:
84/01/85
The fault remains saved in the parameter, even if it disappears.
The parameter is reset after the drive is disconnected and then reconnected.
The possible values of this parameter depend on the network card protocol. Consult the manual for the corresponding card.
Code
Description