Schneider Electric 61 Manual De Usuario

Descargar
Página de 131
118
CiA402 standard configuration and adjustment parameters
 
Code
Description
SMIL
Parameter name:
Minimum speed
CiA402 name:
vl velocity min speed
DRIVECOM name:
Speed-Min-Amount
Logic address:
8607 = 16#219F
and 8608 = 16#21A0
Type:
UDINT
CANopen index:
6046/1
Read/write:
R/W
INTERBUS index:
6046/1
Unit:
rpm
DeviceNet path:
8C/01/08
Parameter conforming to CiA402 profile
32-bit word (low order: 8607, high order: 8608). High orders always = 0.
Writing this parameter also modifies:
[Low speed]
 
(LSP)
• ODVA low speed limit 
(LSPd)
SMAL
Parameter name:
Maximum speed
CiA402 name:
vl velocity max speed
DRIVECOM name:
Speed-Max-Amount
Logic address:
8609 = 16#21A1
and 8610 = 16#21A2
Type:
UDINT
CANopen index:
6046/2
Read/write:
R/W
INTERBUS index:
6046/2
Unit:
rpm
DeviceNet path:
8C/01/0A
Parameter conforming to CiA402 profile
32-bit word (low order: 8609, high order: 8610). High orders always = 0.
Writing this parameter also modifies:
[High speed]
 
(HSP)
• ODVA high speed limit 
(HSPd)
SPAL
Parameter name:
Acceleration speed delta
CiA402 name:
vl velocity acceleration/delta speed
DRIVECOM name:
Speed-Acceleration/Delta speed
Logic address:
8611 = 16#21A3
and 8612 = 16#21A4
Type:
UDINT
CANopen index:
6048/1
Read/write:
R/W
INTERBUS index:
6048/1
Unit:
rpm
DeviceNet path:
8C/01/0C
Parameter conforming to CiA402 profile
Speed for calculation of acceleration ramp.
32-bit word (low order: 8611, high order: 8612).
If writing registers 8611 and 8612 in succession, write register 8611 first, then register 8612.
Writing this parameter also modifies:
[Acceleration]
 
(ACC)
• ODVA acceleration time