Schneider Electric 61 Manual De Usuario

Descargar
Página de 131
21
CiA402 profile
 
6 - Quick stop active
Emergency stop
The drive performs a fast stop, after which restarting will only be possible once the drive has changed to the "Switch on disabled" state.
During fast stop, the drive is unlocked and power is supplied to the motor.
The configuration parameters cannot be modified.
The condition for transition 12 to the state "2 - Switch on disabled" depends on the value of the parameter "Quick stop option code" (QSTD):
• If the "Quick stop option code" parameter has the value 2, the drive stops according to the fast stop ramp and then goes into the state 
"2 - Switch on disabled".
• If the "Quick stop option code" parameter has the value 6, the drive stops according to the fast stop ramp and then remains in the 
state "6 - Quick stop active" until:
- A "Disable voltage" command is received
- Or the STOP key is pressed
- Or there is a freewheel stop command via the terminals
7 - Fault reaction active
Transient state during which the drive performs an action appropriate to the type of fault.
The drive function is activated or deactivated according to the type of reaction configured in the fault management parameters.
8 - Fault
Drive faulty.
The drive is locked, no power is supplied to the motor.
Summary
State
Power section line supply for 
separate control section
Power supplied to motor
Modification of configuration 
parameters
1 - Not ready to switch on
Not required
No
Yes
2 - Switch on disabled
Not required
No
Yes
3 - Ready to switch on
Not required
No
Yes
4 - Switched on
Required
No
Yes, return to "2 - Switch on 
disabled" state
5 - Operation enabled
Required
Yes, apart from an open-loop 
drive with a zero reference or in 
the event of a "Halt" command 
for an open-loop drive.
 No
6 - Quick stop active
Required
Yes, during fast stop
No
7 - Fault reaction active
Depends on fault management 
configuration
Depends on fault management 
configuration
-
8 - Fault
Not required
No
Yes