Installing the Current Transformers
The three models of PowerLogic EM4800 meter use current transformers 
(CTs) with different secondary outputs. The PowerLogic EM4833 meter uses 
split-core 0.333V CTs (see Figure 12), and the PowerLogic EM4880 meter 
uses 80mA CTs only (see Figure 13) and is typically used where accuracy is 
important and long secondary CT wiring is required (up to 300 feet [91.44 
meters]). The PowerLogic EM4880 meter can also use a 5A CT if a 5A 
converter has first been installed.
The PowerLogic EM4805 uses 5A secondary CTs. For instructions, see 
“Installing the 5A CTs on the PowerLogic EM4805” on page 27.
Current transformers connect to the PowerLogic EM4833 and PowerLogic 
EM4880 meters through the 50-conductor CT cable provided with the meter. 
Table 2 describes the CT wire pairs and the cable color scheme for each 
meter point. You can also find this information on the inside of the meter’s 
outer cover.
Each CT has an X1 (positive) and X2 (neutral) wire pair and uses butt-splice 
connectors to attach the CT to a specific meter wire pair. The direction of the 
energy flow is indicated on the CT.
Figure 12:  PowerLogic EM4833 split-core 0.333V current transformer 
3
1
2
THIS
SIDE
TOW
ARD
S SO
UR
CE
4
5
Legend:
1  Source
2  Energy flow
3  Load
4  X1
5  X2