Installation 
© 201
 Schneider Electric All Rights Reserved
19
For a 600Y/347V or higher three-phase wye panel with potential 
transformers with the 120V variant of the meter:
Connect meter terminal A to the voltage disconnect phase A (red wire)
Connect meter terminal B to the voltage disconnect phase B (black 
wire)
Connect meter terminal C to the voltage disconnect phase C (blue wire)
Connect meter neutral terminal to neutral bar in the voltage disconnect 
panel (white wire)
Connect earth wire to earth post using lug provided
Install power supply shorting jumpers (see Figure 10)
NOTE: For the wiring of the potential transformers, see Figure 5.
Figure 10:  PowerLogic EM4800 meter 600Y/347V or higher three-phase 
wye service with potential transformers connection 
Legend:
1     BX cable 
2     Earth
3     Phase C (blue)
4     Phase B (black)
5     Shorting jumper
6     Sense voltage terminal block (J3)
7     Neutral (white)
8     Phase A (red)
9    0.75-inch (1.9-cm) strain relief