EM4800 Series
04/2011
Installation 
© 201
 Schneider Electric All Rights Reserved
31
b.
If the IP address is not 169.254.0.10,  the meter has acquired an 
IP address from the local network, and will be able to report data 
and synchronize time.
3.
Press the Display button until the “Send” command appears on the 
display.
4.
Press the left or right arrow button to manually force the PowerLogic 
EM4800 meter to report metering data using the Ethernet or modem 
connection. This clears data from the PowerLogic EM4800 meter 
memory, and ensures the time is set correctly.
Pulse Inputs
There are two pulse in terminal blocks in the PowerLogic meter, as shown in 
Figure 15. Each terminal block has a negative terminal pin on the right and a 
positive terminal pin on the left. The pulse inputs are compatible with both dry 
and solid-state form A contacts, 10 Hz (maximum), 20 ms pulse width 
(minimum). The inputs are not polarity-sensitive to dry relay contacts. When 
the pulsing device provides solid-state form A outputs, the negative terminal 
from the source device must be connected to the negative terminal of the 
PowerLogic meter pulse in terminal block. 
Display Navigation
The PowerLogic EM4800 meter has three buttons to control the information 
presented on the LCD. The display has a normal and a diagnostics mode. 
The PowerLogic EM4800 meter starts in normal mode, and enters 
diagnostics mode when the Display button is pressed and held for 5 seconds. 
To adjust the contrast, hold down the Display button, and use the right and 
left arrow buttons to increase and decrease the contrast respectively. 
Normal Mode
In Normal mode, the Display button scrolls through the information for each 
meter. The left and right arrow buttons select the previous or next meter 
points respectively. The following information is available:
Real Energy Delivered kWh D
Real Energy Received kWh R
Real Power Watts
Reactive Energy Delivered KVarhD
Reactive Energy Received KVarhR
Reactive Power Var
In Normal mode, the right and left arrow buttons scroll the display from meter 
points 1 to 8, 1 to 12, or 1 to 24, depending on your configuration. 
Diagnostics Mode
Diagnostics mode is accessed by pressing and holding the Display button for 
5 seconds. In Diagnostics mode, pressing the Display button will scroll 
through the following additional information:
Send data command 
CT Primary value and Real Power Watts per phase
Voltage per phase
Local IP address
Reset factory default IP address command
Date and time (UTC)