Schneider Electric E4800 Manual De Usuario

Descargar
Página de 48
PowerLogic
TM 
EM4800 Series
 930-110-01-B.00
Introduction 
04/2011
© 201
 Schneider Electric All Rights Reserved
2
Table 1:  PowerLogic EM4800 series meter specifications 
Specification
PowerLogic EM4833 meter
PowerLogic EM4880 meter
PowerLogic EM4805 meter
Dimensions
Height: 13.125 in. (33.5 cm)
Width: 12 in. (30.5 cm)
Depth: 2.125 in. (5.5 cm)
Height: 13.125 in. (33.5 cm)
Width: 12 in. (30.5 cm)
Depth: 2.125 in. (5.5 cm)
Height: 13.125 in. (33.5 cm)
Width: 17 in. (44 cm)
Depth: 2.125 in. (5.5 cm)
Weight
8.77 lb (3.98 kg)
8.77 lb (3.98 kg)
11.9 lb (5.4 kg)
Sense voltage
100V to 300V 50/60Hz 
2W+N+Protective Earth Wye 
3W+N+Protective Earth Wye 
3W+Protective Earth Delta
100V to 300V 50/60Hz 
2W+N+Protective Earth Wye 
3W+N+Protective Earth Wye 
3W+Protective Earth Delta
100V to 300V 50/60Hz 
2W+N+Protective Earth Wye 
3W+N+Protective Earth Wye 
3W+Protective Earth Delta
Control voltage and current
North America: 120V 125 mA 60 Hz
International: 230-240V 63 mA 
50/60 Hz
North America: 120V 125 mA 60 Hz
International: 230-240V 63 mA 
50/60 Hz
North America: 120V 125 mA 60 Hz
International: 230-240V 63 mA 
50/60 Hz
Current transformers
Measurement Category III
0.333 V secondary CT
Note: All CTs used with the product 
must be UL recognized/listed.
80 mA secondary CT 
200 A primary CT
Meter burden: 4.04 ohms
CT burden: 20 ohms
Part number: METSECT80200
Note: All CTs used with the product 
must be UL recognized/listed.
5 A secondary CT
Note: All CTs used with the product 
must be UL recognized/listed.
Measurement accuracy
(Accuracy compliant when 
used with 0.3% CTs)
ANSI C12.20 Class 0.5
IEC 62053-22 Class 0.5S
ANSI C12.20 Class 0.5
IEC 62053-22 Class 0.5S
Measurement Canada Approved
EG07 compliant
ANSI C12.20 Class 0.5
IEC 62053-22 Class 0.5S
Measurement Canada Approved 
EG07 compliant
Pulse inputs 1 and 2 
Dry form A and solid-state form A 
compatible
Maximum frequency 10 Hz 
Minimum pulse width 20 ms
Dry form A and solid-state form A 
compatible
Maximum frequency 10 Hz 
Minimum pulse width 20 ms
Dry form A and solid-state form A 
compatible
Maximum frequency 10 Hz 
Minimum pulse width 20 ms
Non-volatile memory storage
120 days in 15-minute intervals
120 days in 15-minute intervals
120 days in 15-minute intervals
Onboard modem
V.90
V.90
V.90
Onboard Ethernet port
10/100 Mb/s
10/100 Mb/s
10/100 Mb/s
Serial port
115 kb/s
115 kb/s
115 kb/s
Fuse rating (F1)
North America:120V: T125 mA, 250V
International 230V: T63 mA, 250V
North America:120V: T125 mA, 250V
International 230V: T63 mA, 250V
North America:120V: T125 mA, 250V
International 230V: T63 mA, 250V
Environmental
Operating temperature
-40 to 70
o
C
-40 to 70
o
C
-40 to 70
o
C
Operating humidity
5% to 90% non-condensing
5% to 90% non-condensing
5% to 90% non-condensing
Usage environment
Indoor or enclosed outdoor 
environment 
Indoor or enclosed outdoor 
environment 
Indoor or enclosed outdoor 
environment 
Maximum altitude
9843 ft (3000 m)
9843 ft (3000 m)
9843 ft (3000 m)
Pollution degree
2
2
2