Diagnostics
© 2006 Schneider Electric. All Rights Reserved.
15
EN
G
L
IS
H
Interpreting Statistics
Statistic
Description
Ethernet
Link Status
A status string that represents the speed and 
duplex setting being used to communicate with 
the linking partner.
Frames Transmitted OK
A counter that increments each time a frame is 
successfully transmitted.
Collisions
A counter that increments each time a frame is 
retransmitted due to collision detection.
Excessive Collisions
A counter that increments each time a frame is 
not able to be sent due to reaching the 
maximum collision status based on the 
Truncated Binary Exponential Backoff 
algorithm.
Frames Received OK
A counter that increments each time a frame is 
successfully received.
CRC Errors
A counter that increments each time a frame is 
received that has a checksum/CRC that does 
not match what is calculated.
Alignment Errors
A counter that increments each time a frame is 
received that has a checksum/CRC error and 
does not end on an 8-bit frame boundary.
Frames Too Long
A counter that increments each time a frame is 
received that is larger than the allowed 
maximum size defined in the standards (frames 
larger than 1518 bytes).
Frames Too Short
A counter that increments each time a frame is 
received that is smaller than the allowed 
minimum size defined in the standards (frames 
smaller than 64 bytes).
Modbus TCP/IP
Frames Sent
A counter that increments each time a frame is 
sent.
Frames Received
A counter that increments each time a frame is 
received.
Protocol Errors
A counter that increments each time an 
ill-formed message is received.
Active Connections
c
A status value that represents the number of 
connections that are active at the moment the 
diagnostics page is refreshed. A maximum of 
32 connections are supported. Clicking Active 
Connections opens a new window with a list of 
all of the active client connections.
Accumulative Connections
c
A counter that increments each time a 
connection is made to the ETG.
Maximum Connections
c
A status value that represents the maximum 
number of connections that were active at any 
given moment.
Inbound Read Messages
c
A counter that increments each time a read 
request message is received.
Outbound Read Messages
d
A counter that increments each time a read 
request message is sent.
Inbound Write Messages
c
A counter that increments each time a write 
request message is received.
Outbound Write Messages
d
A counter that increments each time a write 
request message is sent.
Inbound Reply Messages
d
A counter that increments each time a reply 
message is received.
Outbound Reply Messages
c
A counter that increments each time a reply 
message is sent.
c
 Available when the serial port is in Master mode.
d
 Available when the serial port is in Slave mode