Schneider Electric TSXETG100 Manual De Usuario

Descargar
Página de 19
ConneXium
 Ethernet Gateway
 63230-319-211A1
Setup
2/2006
© 2006 Schneider Electric. All Rights Reserved.
8
ENGLISH
Device List
Before you begin, keep in mind the following:
For master mode usage of the COM port:
Modbus devices do not have to be defined in the Device List, but it helps 
you manage your system.
Master Mode Device List Setup
If you selected Master mode on the Serial Port page, follow the steps below 
to set up the device list:
Figure 4:
Master Mode Topology
Action
Result
1. From the Setup page, click Device List.
Opens the Device List page.
2. Select the number of viewable devices (1 to 
128), then click Apply.
Selects the number of viewable locations that 
can be used to define serial slave devices 
connected to the ETG.
3. In the Local ID text box, type the local ID 
(address) of the serial slave device.
Enters the local address of the device.
4. Repeat step 3 until all of the devices are 
entered.
Enters all of the connected devices.
5. Click Apply.
Updates the Device List settings.
Figure 5:
Device List Page in Master Mode
Ethernet 
Connection
RS485 connection
Serial Slave Devices
Up to 128 serial 
slave devices 
using repeaters
ETG in 
master 
mode