Slave Mode Device List Setup
Serial port slave mode allows serial Modbus master devices to access 
information from serial slave devices across a TCP/IP network. Figure 6 
below illustrates how the devices are connected using the device list 
settings in Figure 7.
If you selected Slave mode on the Serial Port page, follow the steps below 
to set up the device list:
Figure 6:
Slave Mode Topology
2
5
2
3
4
5
6
7
Ethernet 
Connection
ETG in
master mode
IP address:
169.254.0.75
RS485
connection
Serial Slave Devices
RS232 or RS485 
connection
Up to 16 remote IP connections 
with up to 128 serial slave devices 
are possible
ETG in 
slave mode
ETG in master
mode
IP address:
169.254.0.28
Serial Slave Devices
RS485
connection
Action
Result
1. From the Setup page, click Device List.
Opens the Device List page.
2. Select the number of viewable devices (1 to 
128), then click Apply.
Selects the number of viewable locations that 
can be used to define remote Modbus TCP/IP 
devices.
3. In the Local ID text box, type the local ID 
(address) of the serial slave device.
Enters the address of the device that the local 
Modbus master device will use to access the 
remote device.
4. In the Remote ID text box, type the remote 
ID (address) of the serial slave device.
Enters the serial slave address of the remotely 
connected device. 
5. Select the Connection.
Selects the Modbus TCP/IP address to 
associate with the remote ID.
6. Repeat steps 3 through 5 until all of the 
devices are entered.
Enters all of the mapping information for the 
ETG to communicate to the remote devices.
7. Click Apply.
Updates the Device List settings.
Figure 7:
Device List Page in Slave Mode