BACnet Communications - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
262
Table 85
Liebert CRV
™
- Multistate Data
Controller
Liebert iCOM
®
v4
Data Label
Object Type
Instance
Object
Name
Access
Notes
Protocol
Server Class
MultiState_Value
1
4553_1
RD
1 = UPS
2 = AIR
3 = PMP
4 = PDU
Air Temperature
Air Temperature Control Sensor
MultiState_Value
12
5012_1
RW
1 = Supply
2 = Remote
3 = Return
Remote Sensor Temperature
Calculation
MultiState_Value
13
5013_1
RW
1 = Average
2 = Maximum
Fans
Fan Control Mode
MultiState_Value
24
5047_1
RW
1 = Internal (Auto)
2 = External (Manual)
Fan Control Sensor
MultiState_Value
25
5052_1
RW
1 = Supply
2 = Remote
3 = Return
Remote Sensors 1
Remote Sensor Function
MultiState_Value
36
5058_1
RW
1 = Disable
2 = Reference
3 = Control
Remote Sensors 1
Remote Sensor Function
MultiState_Value
47
5058_2
RW
1 = Disable
2 = Reference
3 = Control
Remote Sensors 10
Remote Sensor Function
MultiState_Value
135
5058_10
RW
1 = Disable
2 = Reference
3 = Control
System Info
System Status
MultiState_Value
146
4123_1
RD
1 = Normal Operation
2 = StartUp
3 = Normal
with Warning
4 = Normal with Alarm
5 = Abnormal Operation
System Operating State
MultiState_Value
147
4706_1
RD
1 = off
2 = on
3 = standby
System Control Mode
MultiState_Value
148
4707_1
RD
1 = Internal (Auto)
2 = External (Manual)
System Operating State Reason
MultiState_Value
149
5074_1
RD
1 = Reason Unknown
2 = Network Display
3 = Alarm
4 = Schedule
5 = Remote System
6 = External Input
7 = Local Display
System Operations
System On/Off Control
MultiState_Value
160
5143_1
RW
1 = off
2 = on