Emerson BACNET IP Manuel D’Utilisation

Page de 372
BACnet Communications - Thermal Management Products
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
262
Table 85
Liebert CRV
 - Multistate Data
Controller
Liebert iCOM
®
 v4
Data Label
Object Type
Instance
Object
Name
Access
Notes
Protocol
Server Class 
MultiState_Value
1
4553_1
RD
1 = UPS 
2 = AIR 
3 = PMP 
4 = PDU 
Air Temperature
Air Temperature Control Sensor 
MultiState_Value
12
5012_1
RW
1 = Supply
2 = Remote
3 = Return
Remote Sensor Temperature 
Calculation
MultiState_Value
13
5013_1
RW
1 = Average
2 = Maximum
Fans
Fan Control Mode 
MultiState_Value
24
5047_1
RW
1 = Internal (Auto)
2 = External (Manual)
Fan Control Sensor 
MultiState_Value
25
5052_1
RW
1 = Supply 
2 = Remote 
3 = Return 
Remote Sensors 1
Remote Sensor Function 
MultiState_Value
36
5058_1
RW
1 = Disable 
2 = Reference 
3 = Control 
Remote Sensors 1
Remote Sensor Function 
MultiState_Value
47
5058_2
RW
1 = Disable 
2 = Reference 
3 = Control 
Remote Sensors 10
Remote Sensor Function 
MultiState_Value
135
5058_10
RW
1 = Disable 
2 = Reference 
3 = Control 
System Info
System Status 
MultiState_Value
146
4123_1
RD
1 = Normal Operation 
2 = StartUp 
3 = Normal
with Warning 
4 = Normal with Alarm 
5 = Abnormal Operation
System Operating State 
MultiState_Value
147
4706_1
RD
1 = off 
2 = on 
3 = standby
System Control Mode 
MultiState_Value
148
4707_1
RD
1 = Internal (Auto) 
2 = External (Manual) 
System Operating State Reason 
MultiState_Value
149
5074_1
RD
1 = Reason Unknown 
2 = Network Display 
3 = Alarm 
4 = Schedule 
5 = Remote System 
6 = External Input 
7 = Local Display 
System Operations
System On/Off Control 
MultiState_Value
160
5143_1
RW
1 = off 
2 = on