GE 500 Manual De Usuario
OPM_MLE_LTE_350_1K0_1GB_V011
7
DE ML Series: user manual 1.1 (GB)
GE Digital Energy
™
ML Series
g
5.1 General
The UPS is virtually maintenance free: take care of proper environmental conditions and keep air inlets-
outlets free of dust. Please read 2.1.
5.2 Fuses
If the AC input fuse (1) is defective, be sure it is replaced by a compatible fuse from the same make and
type. Fuse ratings: see chapter 7.
5.3 Batteries
5.3.1 General
The service life of the battery is up to 6 years.
As a healthy battery is critical to the UPS, keypad 'ON' allows a battery test (3.2.2). When the condition of
the battery is critical, a 'replace battery' alarm will be given (see 3.3). Charge the batteries for at least 10
hours, switch the UPS off and back on, and perform a self test. If the alarm persists replace the batteries
as soon as possible.
5.3.2 Battery replacement
•
Warning: first read the safety rules in section 1.2.
•
When replacing the batteries, use the same number and voltage(V)/capacity(Ah).
•
Proper disposal or recycling of the batteries is required. Refer to your local codes for disposal
requirements.
•
Never dispose of batteries in a fire: they may explode.
•
Do not open or mutilate batteries: their contents (electrolyte) may be extremely toxic. If exposed to
electrolyte, wash immediately with plenty of water.
•
Avoid charging in a sealed container.
•
Never short circuit batteries. When working with batteries, remove watches, rings or other metal
objects, and only use insulated tools.
Battery replacement procedure (ML 350/500/700)
NOTE: This procedure refers to the ML 350/500/700 models only. The batteries of the ML 1000 are not
user replaceable, please contact your dealer.
1 press keypad “OFF’ and remove the UPS input power cord from the AC mains supply
2 remove UPS front panel (two screws on bottom side)
3 pull out the battery and disconnect the battery wires
4 connect the new battery (black -, red +); small sparks can occur, this is normal
5 reinstall the new battery, do not pinch or clamp the wires
6 reinstall UPS front panel.
5 - Maintenance