Whenever a malfunction occurs, first check external factors (e.g. connections, temperature, humidity or 
load) to determine whether the problem is caused by the unit itself or by its environment. Subsequently 
check the input fuse: it may be blown. If so: replace the fuse (see 5.2) and be sure that the UPS is not 
overloaded. 
The following chart is a simple troubleshooting checklist only. If the suggested solution does not succeed, 
or if the information is insufficient to solve the problem, please contact your dealer or consult 
www.gedigitalenergy.com. 
 
PROBLEM 
POSSIBLE CAUSE 
SOLUTION 
Blown input fuse 
Output overload 
Reduce load, replace fuse 
 
System failure 
Please contact your dealer or 
consult www.gedigitalenergy.com 
No output voltage during self 
test (3.2.2) 
System failure 
Please contact your dealer or 
consult www.gedigitalenergy.com 
Only battery start possible 
Blown input fuse 
See above 
No communication between 
computer and UPS 
Computer interface problem 
Check interface cable and 
attached computer. 
Blown input fuse 
See above 
UPS operates on battery 
though mains is present 
Very high, low or distorted 
mains voltage 
Check mains voltage, contact 
qualified electrician 
Continuously sounding 
buzzer 
mains present 
UPS overload 
Reduce load 
Continuously sounding 
buzzer 
mains not present 
UPS overload in battery mode 
Reduce load 
UPS does not provide the 
expected back-up time, no 
alarm ‘replace battery’ 
Weak battery: recent outage or 
worn out battery 
Charge the battery. If the battery is 
near the end of its service life, 
consider replacing the battery 
even if the ‘replace battery’ alarm 
is not yet active. 
Battery test just after 
installation or mains failure 
Allow the UPS to recharge the 
batteries 
Blinking LED ‘BAT’, 
intermittent buzzer 
Weak battery 
Read 5.3 
UPS output switches OFF 
Battery depleted during mains 
failure: end of runtime 
Wait until mains returns 
Load is less than 5% of rated 
output and no mains power is 
present (no-load shutdown 
function is active) 
Wait until mains returns 
 
Load is more than 150% of 
rated output 
Reduce load 
6  -  Troubleshooting