15/88 Operating 
Manual 
SG Series 10, 20, 30 & 40 kVA 
3.3.2  Features of RPA parallel system 
The 
SG Series  parallel system is designed to provide a complete Redundant Parallel 
Architecture, and is free from common equipment. 
Not only the Inverters are redundant, but also the Bypass functions are designed with 
redundant modular concept. 
 
When one UPS needs maintenance or service, the Load is powered by the other units 
supplying the Load
 bus. 
 
The redundant communication bus to which all units are connected keeps each unit informed 
about the status of all the other units. 
 
The  control panel located on each unit allows controlling and monitoring the status of this 
unit. 
 
 
 
3.3.3 System 
control 
high-speed redundant, serial communication bus guarantees the exchange of data and 
thus the communication between the CPU's of each unit. 
 
Each module controls it's own function and operational status and communicates with all other 
modules, in order to act or react if necessary, adapting it to the new conditions. 
 
 
 
3.3.4 Synchronization 
All units are identical, but one unit is arbitrarily selected as the reference and all the other units 
synchronize to this unit, which in turn, synchronizes to the Utility Bypass voltage, as long as 
the later is within tolerances. 
 
In case of reference failure, another unit in the parallel system is automatically chosen to take 
over the reference role. 
 
The Bypass Input for all the units of the parallel system must be supplied from the same AC 
source (no phase shift allowed between them). 
 
 
 
3.3.5  Load sharing  
On each unit of the parallel system, Inverter Output Voltage and Current are measured and 
applied to a Load sharing bus. 
 
An eventual difference between the units is therefore automatically equalized. 
 
 
It is strongly recommended that no transformers, automatic circuit 
breakers or fuses should be inserted between the unit’s output and the 
Load
 common bus bars. 
However, it is recommended that a disconnect or isolation switch be 
inserted.