GE 30 Manual De Usuario

Descargar
Página de 88
 
GE
 
OPM_SGS_USM_10K_40K_0US_V010.doc 
16/88 Operating 
Manual 
SG Series 10, 20, 30 & 40 kVA 
3.4 
RECTIFIERS PARALLELED ON THE SAME BATTERY 
 
A parallel system with a Common Battery for two or more Rectifiers
requires a particular installation and adequate setting of some 
parameters, (accessible only through password), and can therefore 
only be done by a qualified engineer from GE.
 
 
Usually each Rectifier-Inverter Unit runs with its own Battery
In case of parallel units are running with a Common Battery (max. 4 UPS - see Fig 4.12-1), the 
sharing circuit between individual Rectifier is integrated in the communication bus of the 
system in order to assure an equal sharing of the Rectifiers output currents. 
 
 
Fig. 3.4-1   Diagram RPA system with Rectifiers on Common Battery 
1 – 
2 – 
3 – 
4 – 
5 – 
6 – 
7 – 
8 – 
Rectifier 
Inverter 
Automatic Bypass 
Manual Bypass 
Mains Power 
Load Bus Bar 
External Battery Fuse 
Battery 
 
Pay attention to the following recommendations: 
• 
The units delivered for this functioning mode needs a special parameters setting, so they 
must be prepared in advance before the installation. 
• 
The installation must be performed only with the UPS system must be completely shut 
down. 
• 
The AC Rectifiers input power (5) must be the same, with clockwise phase rotation for each 
unit. 
• 
Each Rectifier must be set for the same floating DC voltage and the same Battery current 
limitation. 
• 
It is recommended to install the fuses / MCB (7) on each line connecting the Rectifiers to 
the common Battery for maintenance / safety reasons. 
• 
In case one must be powered down for maintenance, switch-OFF the concerned unit before 
open the DC fuses / MCB on the Battery line (7). 
• 
It is recommended to connect an external NO free contact “Battery Fuses” to the UPS and 
to enable the function by setting the parameter (see Section 7.1). 
• 
If an emergency generator set supply the UPS, and the free contact “Generator ON” is 
connected to the Customer interface, connect a separate NO free contact on each parallel 
unit. 
• 
The parameters enabling the Battery test, both manual and automatic, must be set in the 
same mode on all the units having the Rectifiers on Common Battery
• 
Do not connect the temperature sensor for automatic battery floating voltage compensation. 
• 
Do not enable the function Boost charge (parameter 87).