GE 30 Manual De Usuario

Descargar
Página de 88
 
GE
 
OPM_SGS_USM_10K_40K_0US_V010.doc 
68/88 Operating 
Manual 
SG Series 10, 20, 30 & 40 kVA 
7.4.2  Maintenance system shutdown (Load supplied from Q2 on all Units) 
 
Initial status: Load supplied from all Inverters
 
 
First operated unit 
All other units of the system 
 
 
1. Press and hold inverter off 
( O ) 
key on all Units, until the LED inside the Inverter 
symbol turns OFF. 
At no redundancy, the system will transfer to Utility supply. 
 
 
First operated unit
 
All other units of the system
 
 
 
2. Close Q2 
(Pos. I) 
on all Units
Load is now supplied from Utility in parallel from Bypass and Manual Bypass Q2 of all Units
 
 
First operated unit
 
All other units of the system
 
 
 
3. Open Q1 
(Pos. O) 
and press total off button on all Units. 
The Bypass of all Units will disconnect and all Rectifiers are shutdown. 
 
 
First operated unit
 
All other units of the system
 
 
 
4.  Disconnect the Battery from all Units. 
• 
Wait 5 minutes for DC-Link Capacitors discharge. 
 
 
First operated unit
 
All other units of the system
 
 
 
End of procedure