7.4.3  From Manual Bypass (Q2) to normal function On-line 
 
Initial status: Load supplied from Manual Bypass. 
All Q2 of the system closed. 
 
 
First operated unit 
All other units of the system 
 
 
1.  Connect the Battery to all Units by closing the external Battery Switch(es) or 
Fuses
 
 
2.  Close Q1 (Pos. I) on all Units. 
The  Rectifiers will start automatically and at the closure of Q1 of the last Unit, the 
Bypass of all Units will be activated. 
 
 
First operated unit
 
All other units of the system
 
 
 
3.  Open Q2 (Pos. O) on all Units
 
 
First operated unit
 
All other units of the system
 
 
Continue