6  Commissioning 
Issue 10/06 
 
MICROMASTER 440 
52 
Operating Instructions (Compact) 
 
Control word of motor model
 
 
This parameter controls the operation of the sensorless vector control (SLVC) at very low 
frequencies.
 
This therefore includes the following conditions: 
Bit00  Start SLVC open loop          0 NO  1 YES
  
(Operation directly after an ON command) 
Bit01  Zero crossing SLVC open loop  0 NO  1 YES
 
(zero crossing) 
f
t
p1755
Closed loop
Open loop
Start
f
t
Closed loop
Open loop
Zero crossing
p1755
p1755
 
For most applications the setting of parameter p1750 = 0 gives the best result at low 
frequency. 
 
Start-freq. motor model (SLVC) 
Enter the start frequency of sensorless vector control (SLVC), thereby SLVC switches over 
from open-loop to closed-loop at that frequency. 
 
.
.
r0062
Speed
controller
Pre-
control
Torque
limitation
Current
controller
i
sq
open/closed
loop
Flux setpoint
closed loop
Flux setpoint
open loop
i
sd
p1610
p1611
+
+
0
Act. output
voltage
Act. output
frequency
Act. frequency
Current
measurement
Act. angle
Observer model
closed loop
Slip
Frequency
setpoint
i
u
i
w
i
v
p1452
p1470 p1472
p1750/p1755
P1750 = ... 
P1755 = ... 
1
 
5.0 Hz