6  Commissioning 
MICROMASTER 440   
Operating Instructions (Compact) 
53
 
6.4.17.2 
Vector control with encoder (VC) 
¾
  First step: Parameterizing the speed encoder (refer to Section 6.4.15) 
¾
  When commissioning Vector Control with encoder-feedback (VC), the drive 
should be configured for V/f mode (see p1300) first. Run the drive and compare 
r0061 with r0021 that should agree in: 
− sign 
−  magnitude (with a deviation of only a few percent) 
Only if both criteria are fulfilled, change p1300 and select VC (p1300 = 21/23). 
¾
  Encoder loss detection must be disabled (p0492 = 0) if torque is limited 
externally., e.g.: 
− closed-loop winder control 
−  traversing / moving to a fixed endstop 
−  when using a mechanical brake 
 
Control mode 
21  Vector control with sensor 
 
Filter time for act. speed
 
 
Sets time constant of PT1 filter to smooth actual speed of speed controller. 
Decreasing the value leads to a higher dynamic of the speed regulation. Instability is seen if 
the value is to low. p1442 = 2 can be set for most applications. 
 
Gain speed controller
 
 
Enters gain of speed controller. 
 
Integral time speed controller
 
 
Enters integral time of speed controller. 
 
Precontrol
Freq. setpoint
r1438
r1084
Kp
Tn
p1460 p1462
r0064
Torque
setpoint
p1496 p0341 p0342
p1442
Act. frequency
from encoder
r0063
r1170
p1492
p1489
p1488
Droop
r1490
150 ms
r1518
0
1
0
r0079
r1508
*)  only active, if pre-control is enabled
     (p1496 > 0)
*)
 
P1300=21 
0
 
4 ms
 
3.0
 
P1442 = ... 
P1460 = ... 
P1462 = ... 
400 ms