Xantrex Technology SW Plus 4048 Manual De Usuario

Descargar
Página de 344
Inverter Specifications
A–12
976-0043-01-02
Inverter Capacity versus Temperature
The output power of the inverter diminishes as ambient temperature rises.  
However, as can be seen below, with the exception of the SWP5548, these 
inverters are sized to be able to run a full rated output power up to 40C.  
However, it should be noted that the overcurrent circuit on the unit is 
temperature compensated to protect the unit and that the thermal circuit 
breaker will trip at a lower current as the temperature rises.  Therefore, the 
surge ability of the unit decreases with increased temperature.  
This table refers to output VA only.  Testing was conducted in a thermal 
chamber with the inverters as stand-alone units without accessories.
Table A-1 Derating from continuous power (VA) at elevated ambient 
temperatures
Model
25° C
30° C
35° C
40° C
SW Plus 2524
No Derating
No Derating
No Derating
No Derating
SW Plus 2548
No Derating
No Derating
No Derating
No Derating
SW Plus 4024
No Derating
No Derating
No Derating
No Derating
SW Plus 4048
No Derating
No Derating
No Derating
No Derating
SW Plus 5548
No Derating
No Derating
No Derating
5.3KVA