Time versus Current
976-0043-01-02
A–13
Time versus Current
Loads presented to the inverter are seldom constant. Typically, large loads 
are operated for only short periods of time. In order to provide the 
maximum utility, Xantrex inverters are allowed to operate at power levels 
that exceed their continuous power ratings. This graph shows how loads 
that are larger than the inverter can sustain continuously can be operated 
for useful periods of time.
The length of time that the inverter can operate at high power is limited by 
temperature. When large loads are run, the inverter’s temperature 
increases. At the point where more heat is created in the inverter than can 
be dissipated, its ability to operate becomes time limited. 
Figure A-9 Time versus Current for the Sine Wave Plus 2524