Xantrex Technology SW Plus 4048 Manual De Usuario

Descargar
Página de 344
Basic Setup Menu
976-0043-01-02
B–5
Basic Setup Menu
 provides a list of Basic Setup Menu headings and menu items, 
with available set points. This table also provides the default settings for 
each menu item as programmed in the factory. The last column “User 
Settings” is provided for you to write in the settings specific to your 
installation.
Table B-2 Basic Setup Default and User Settings for the Sine Wave Plus 2524 and 2548 Models
Sine Wave Plus
 2524
Sine Wave Plus
 2548
User 
Settings
Basic Setup Menus 
Range/
Display
Default
Range/
Display
Default
10 Time of Day Setup Menu
See 
 for details.
10A Set Hour 
00:00:00 to 
23:50:00
00:00:00
00:00:00 to 
23:50:00
00:00:00
10B Set Minute
00:00:00 to 
00:09:00
00:00:00
00:00:00 to 
00:09:00
00:00:00
10C Set Second
00 to 59
00:00:00
00 to 59
00:00:00
11 Inverter Setup Menu
See 
 for details.
11A High Battery Cut Out Vdc 
16.1 to 34.0 
32.0 
32.2 to 68.0 
64.0 
11B Low Battery Cut In Vdc
16.1 to 33.9 
26.0 
32.2 to 67.8 
52.0 
11C Low Battery Cut Out Vdc
11.0 to 33.9 
22.0 
32.0 to 67.8 
44.0 
11D LBCO Delay Minutes
01 to 255
15
01 to 255
15
11E Search Watts (SRCH)
00 to 248
08
00 to 248
08
12 Battery Charging Menu
See 
 for details.
12A Finish Stage
SILENT 
FLOAT
FLOAT
SILENT 
FLOAT
FLOAT
12B Bulk Volts DC
20.0 to 32.0 
28.8 
40.0 to 64.0 
57.6 
12C Float Volts DC
20.0 to 32.0 
26.8 
40.0 to 64.0 
53.6 
12D Equalize Volts DC
20.0 to 32.0 
28.8 
40.0 to 64.0 
57.6 
12E Max Charge Amps AC
01 to 20
20
01 to 20
20
12F Bulk Done Amps AC
00 to 45
10
00 to 45
10
12G EQ Vdc Done Timer
00:00 to 
23:50
02:00
00:00 to 
23:50
02:00
12H Max Bulk/EQ Timer
00:00 to 
23:50
05:00
00:00 to 
23:50
05:00