Configuration Settings
B–6
976-0043-01-02
12I Temp Comp
LeadAcid 
NiCad
LeadAcid
LeadAcid 
NiCad
LeadAcid
13 AC Inputs Menu
See 
 for details.
13A Grid (AC1) Amps AC
00 to 60
60 
00 to 60 
60 
13B Gen (AC2) Amps AC
00 to 60 
30 
00 to 60 
30 
13C Input Upper Limit Vac
125 to 150 
130 
125 to 150 
130 
13D Input Lower Limit Vac
80 to 115 
110 
80 to 115 
110 
14 Save/Restore Settings Menu
See 
 for details.
14A Push INV now to save 
settings
Push INV now to Save Settings
14B Push GEN to restore settings 
Push GEN to restore settings
14C Push GEN for factory 
defaults
Push GEN for factory defaults
Table B-3 Basic Setup Default and User Settings for the Sine Wave Plus 4024 and 4048 Models
Sine Wave Plus
 4024
Sine Wave Plus
 4048
User 
Settings
Basic Setup Menus 
Range/
Display
Default
Range/
Display
Default
10 Time of Day Setup Menu
See 
 for details.
10A Set Hour 
00:00:00 to 
23:50:00
00:00:00
00:00:00 to 
23:50:00
00:00:00
10B Set Minute
00:00:00 to 
00:09:00
00:00:00
00:00:00 to 
00:09:00
00:00:00
10C Set Second
00 to 59
00:00:00
00 to 59
00:00:00
11 Inverter Setup Menu
See 
 for details.
11A High Battery Cut Out Vdc 
16.1 to 34.0 
32.0 
32.2 to 68.0 
64.0 
11B Low Battery Cut In Vdc
16.1 to 33.9 
26.0 
32.2 to 67.8 
52.0 
11C Low Battery Cut Out Vdc
11.0 to 33.9 
22.0 
32.0 to 67.8 
44.0 
11D LBCO Delay Minutes
01 to 255
15
01 to 255
15
11E Search Watts (SRCH)
00 to 248
08
00 to 248
08
Table B-2 Basic Setup Default and User Settings for the Sine Wave Plus 2524 and 2548 Models
Sine Wave Plus
 2524
Sine Wave Plus
 2548
User 
Settings
Basic Setup Menus 
Range/
Display
Default
Range/
Display
Default