Optiquest iRIS 320 Manual De Usuario

Descargar
Página de 73
 iRIS 220 / iRIS 320, V1.19 User Guide - 8 
 
8
 
iQuest (NZ) Ltd  - PO Box 15169, Hamilton, New Zealand  Tel: +64 7 857-0810  Fax: +64 7 857-0811  Email: iquest@iquest.co.nz
 
 

   
2.6 Technical Specifications – iRIS 220 
 
Dimensions: 
100mm x 172mm x 40mm (3.93in x 6.77in x 1.57in) 
 
 
 
(Excluding connectors) 
 
Mass: 
380g (13.4oz) 
 
Power Supply: 
External regulated 12V dc power supply or rechargeable sealed lead-acid battery. 
 
Charger Source - External 15-30V dc supply.  Supports a directly connected solar 
panel (no regulator required). 
 
Power Consumption: 
Less than 3mA @ 12V in idle mode and full power save mode selected. 
Actual current consumption is dependent on power management mode, wireless 
modem state and I/O configuration. 
 
Comms Interfaces: 
1x RS232 DB9, 38400 bps, DTE configuration. 
1x Integral dual-band (900/1800MHz) GSM/GPRS modem or 
    Integral single-band (1900MHz) GSM/GPRS modem or 
    Integral CDMA/CDMA-X modem  
 
Digital I/O: 
2 x Digital Inputs 
 - 30Vdc maximum input, switch to 0Vdc to activate. 
 - Link selectable for either mechanical (<20Hz) or electronic (<5kHz) switching. 
 
2 x Digital Outputs 
 - 1 x Switched 12V out (max 300mA) 
 - 1 x Open-drain pull-down (max 300mA @ 30V) 
 
Analog I/O: 
4 x 12 bit uni-polar analog inputs. Range 0-5000mV.  Input impedance 98k
Ω
Referenced to 0V common.  Internal measurements available for monitoring are: 
 
Battery Voltage 
 
Supply Voltage 
 
Internal Temperature (
°
C or 
°
F) 
 
Received Signal Strength Indication (RSSI) 
 
Logging Memory: 
Non-volatile 2MB flash storage of 262,144 time/date stamped data points.  Circular 
buffer mode (overwrites oldest data when memory is full).  
A typical site with 2 parameters logged every 15 minutes plus battery voltage logged 
hourly will give 3.3 years of storage before data overwrite occurs. 
 
Clock/Calendar: 
Non-volatile with integral lithium back-up battery.  Leap year recognition. Accurate to 
+/-20 secs month, trimmable via a configuration register. 
 
Mounting: 
 
4 x M4 (3/16”) mounting holes at ends of case.  
 
Environmental: 
Storage Temperature:   -20
°
C - +85
°
C. (-4
°
F - +185
°
F) 
 
Operating Temperature:  -10
°
C - +70
°
C. (14
°
F - +158
°
F)