3  Commissioning 
Issue 03/01 
 
MICROMASTER 411 & COMBIMASTER 411    Operating Instructions  
56 
6SE6400-5CA00-0BP0  
3.4 General 
operation 
For a full description of standard and extended parameters refer to the Parameter 
List. 
 
NOTICE 
1.  The inverter does not have a main power switch and is live when the power 
supply is connected. It waits, with the output disabled, until the RUN button is 
pressed or for the presence of a digital ON signal at terminal 1 (ON/OFF1). 
2.  If a BOP or an AOP is fitted and the output frequency is selected to be 
displayed (P0005 = 21) the corresponding setpoint is displayed approximately 
every 1.0 seconds while the inverter is stopped. 
3.  The inverter is programmed at the factory for standard applications on 
Siemens four-pole standard motors that have the same power rating as the 
inverters. When using other motors it is necessary to enter the specifications 
from the motor's rating plate. See Figure 3-7 for details on how to read motor 
data. 
4.  Changing motor parameters is not possible unless P0010 = 1 and P004 = 0 
or 3. 
5.  You must set P0010 back to 0 in order to initiate a run. 
 
3.4.1 Default 
Operation 
For default operation, connect the terminals as shown in the figure below: 
8      9
1      2       3      4      5       6       7
 
Figure 3-8 
Default Setup Terminal Connections 
FREQUENCY SETPOINT 
Setpoint addition: Control potentiometer and Analog input (P1000 = 27).