3  Commissioning 
Issue 03/01 
 
MICROMASTER 411 & COMBIMASTER 411    Operating Instructions  
58 
6SE6400-5CA00-0BP0  
3.4.3 
Non - Default Modes of Operation 
Non-default modes of operation require the use of either a Keypad (BOP or AOP) 
or a Commissioning tool (Drive Monitor or Starter) in order to change from the 
default parameter settings. 
The BOP, Part Number: 6SE6400-0BP00-0AA0 is housed in an Operator Panel 
Mounting Kit, Part Number 6SE6401-1DF00-0AA0 and connected via the Interface 
Link Cable, Part Number 6SE6401-1BL00-0AA0 to the Inverter serial comms port. 
This arrangement is shown in Figure 3-9. 
 
Figure 3-9 
Connect BOP/AOP with the MICROMASTER 411 
Prerequisites 
 
P0010 = 0 (in order to initiate the run command correctly).  
 
P0700 = 1 (enables the start/stop button on the BOP). 
 
P1000 = 1 (this enables the motor potentiometer setpoints).  
 
1.  Press the green Button 
 to start the motor. 
2.  Press the Button 
 while the motor is turning. Motor speed increases to 
50 Hz. 
3.  When the inverter reaches 50 Hz, press the Button 
. Motor speed and 
display is decreased. 
4.  Change the direction of rotation with the
 
Button 
5.  The red button stops the motor