Modbus TCP Remote I/O Communication Module RTU-EN01 
 
DVP-PLC Operation Manual 
„
 Environment 
Noise immunity 
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge 
EFT (IEC 61131-2, IEC 61000-4-4): Power Line:±2KV, Digital Input: ±2KV, 
Communication I/O: ±2KV 
RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 100MHz, 10V/m. 1.4GHz ~ 2.0GHz, 
10V/m 
Conducted Susceptibility Test (EN61000-4-6, IEC61131-2 9.10): 150kHz ~ 80MHz, 
3V/m 
Surge Test (Biwave IEC61132-2, IEC61000-4-5): Power line 0.5KV DM, Ethernet 
0.5KV CM, RS-485 0.5KV CM 
Operation 
0ºC ~ 55ºC (temperature), 50 ~ 95% (humidity), pollution degree 2 
Storage 
-25ºC ~ 70ºC (temperature), 5 ~ 95% (humidity) 
Shock/vibration 
immunity 
International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 
68-2-27 (TEST Ea) 
Certificates 
 
 
„
 Electrical 
specification 
Power supply voltage 
24VDC (-15% ~ 20%) (with DC input polarity reverse protection) 
Power fuse capacity 
1.85A/30VDC, Polyswitch 
Power consumption 
2W 
Insulation voltage 
500VDC 
Weight 116g 
Product Profile & Outline 
2.1 Dimension 
STOP
RS
-4
85
RS
-2
32
RTU-
E
N
01
RUN
BAT.LOW
POWER
RUN
LAN
60
37.4
 
Unit: mm