Modbus TCP Remote I/O Communication Module RTU-EN01 
 
DVP-PLC Operation Manual 
2.4 RUN/STOP Switch 
Status 
Explanation 
1. RUN indicator on RTU-EN01 is ON. 
2. Analog input/output module is in RUN status. 
RUN 
3. Smart PLC function is running. 
1. Analog input/output module switches from RUN to STOP status. 
RUN Æ STOP
2. Y points on digital input/output module are all OFF. 
1. RUN indicator on RTU-EN01 is OFF. 
2. Analog input/output module is in STOP status. 
STOP 
3. Smart PLC function stops. 
1. RTU-EN01 re-detects the information on the right-side module. 
STOP
RUN
 
STOP Æ RUN
2. Analog input/output module switches from STOP to RUN status. 
2.5  RJ-45 PIN Definition 
PIN 
Signal 
Definition 
PIN
Signal 
Definition 
1 Tx+ 
Positive pole for data 
transmission 
5 -- 
N/C 
2 Tx- 
Negative pole for data 
transmission 
6 Rx- 
Negative pole for data 
receiving 
3 Rx+ 
Positive pole for data 
receiving 
7 -- 
N/C 
4 -- 
N/C 
8  -- 
N/C 
 
2.6  RS-232 PIN Definition 
PIN 
Signal 
Definition 
PIN
Signal
Definition 
1 -- 
N/C 
5 Tx  Transmission 
data 
2 -- 
N/C 
6  -- 
N/C 
3 -- 
N/C 
7  -- 
N/C 
4 Rx 
Reception 
data 
8 GND 
Ground 
 
2.7  RS-485 PIN Definition 
PIN 
Signal 
Definition 
SG 
Ground of data 
D- 
Negative pole for data 
D+ 
Positive pole for data 
1
2
3
 
Installation & Wiring 
In this section, we will introduce how to connect RTU-EN01 to other devices and the network. 
3.1  Connecting RTU-EN01 to DVP Slim Series Digital Input/Output Module 
z
  Open the fixing clips on the right top and bottom sides on RTU-EN01. Meet the extension port on RTU-EN01 
and the digital input/output module. 
z
  Press and fix the clips on the digital input/output module. Make sure the contact between the modules is fine.