Power
ProLiant DL160 G5 Fully Configured
115V/60Hz
220V/50Hz
Fully Loaded System Input Wattage (W)
651
638
Fully Loaded System Input Current (A rms)
5.7
3.0
Fully Loaded System Thermal (BTU- Hr)
2218
2174
Fully Loaded System VA (Volt-Amp)
657
657
System Leakage with all power supplies
loaded (mA)
loaded (mA)
1.58
3.03
System Inrush Current with all power
supplies loaded (A)
supplies loaded (A)
19
37
Power cord requirements
Nema 5-15P to IEC320-C13
IEC320-C13 to IEC320-C14
NOTE: Power shown is for a fully configured system consisting of (2) CPU, (8) double-sided DIMMs, (2) HDDs, (1) CD-
ROM, and (2) PCI cards.
ROM, and (2) PCI cards.
Power Cord
AF556A
Server Power Cords
One 6' Highline (IEC-IEC) power cord ships standard
NOTE: HP ProLiant DL servers no longer ship standard with NEMA power cords (163719-002)
that allow connection to 110V US wall outlets in a home or office. ProLiant DL servers are
primarily connected to PDU's in data center racks so they now ship standard with only a PDU
power cord (416151-B21). If a user wishes to power a ProLiant DL server using a 110V receptacle
(NEMA-15), the NEMA power cord (227099-001) must be ordered separately.
that allow connection to 110V US wall outlets in a home or office. ProLiant DL servers are
primarily connected to PDU's in data center racks so they now ship standard with only a PDU
power cord (416151-B21). If a user wishes to power a ProLiant DL server using a 110V receptacle
(NEMA-15), the NEMA power cord (227099-001) must be ordered separately.
If customers require a local power cord, they can check the power cord matrix for the appropriate
cord. Please see the following power cord matrix:
cord. Please see the following power cord matrix:
.