Connection
Carry out the connection to the gas plant
only by means of a rigid metallic pipe
conforming to the regulations in force.
The  joint  for  the  entry  of  gas  into  the
appliance is threaded GJ 1/2".
Carry out the connection avoiding any type
of stress on the appliance.
Natual gas appliances must be fitted with a
pressure regulator  and be installed at the
inlet  connection. The  gas  pressure  must
then be set as a part of the commissioning
procedures.
For  U-LPG  the  pressure  adjustment  is
made via the regulator fitted at the domestic
cylinder.
Important
Upon completion of installation, always
check:
l
that all the joints are completely sealed
by using a soapy solution, never a flame;
l
that  the  gas  pressure  has  been
regulated  to  1.00kPa  for  Natural  Gas
and  2.75kPa  for  Universal-LPG.  The
pressure  test  point  is  located  on  the
regulator for Natural Gas models or at
the top left hand rear of the cooker for
U-LPG models. The pressure should be
measured and adjusted with the Wok
burner on high flame;
l
that  the  automatic  ignition  system  is
operating  satisfactory  on  all  burners,
both individually and in combination;
l
that the burners operate correctly, are
stable,  without  yellow  tipping  or
excessive noise on high and low flame.
Then demonstrate to the customer the
appiance  operation  and  leave  these
instructions.