Schneider Electric 58 TRX Manual De Usuario

Descargar
Página de 232
Class 8998 Motor Control Centers
Space Requirements
215
09/2003
©
 2000–2003 Schneider Electric All Rights Reserved
SPACE REQUIREMENTS
NOTE: In the following tables the horsepower shown is nominal and only for convenience; you should 
size the controller by the actual motor full-load amperage.
Variable Torque 480 Vac Altivar 58 TRX AC Drives
NEMA Type 1 and 1A 
(Gasketed)
NEMA Type 12
Motor Rated Horsepower 
at 460 Vac
Maximum Continuous 
Output Current (A)
Space (Height)
Space (Height)
0.5 to 3 hp
5.8
12”
24”
5 to 7.5 hp
13
15”
24”
10 to 15 hp
24
24”
36”
20 to 25 hp
34
27”
36”
30 to 50 hp
65
45”
45”
60 to 100 hp
124
72” (20” wide)
72” (20” wide)
125 hp
156
72” (25” wide)
Not available
150 to 250 hp
302
72” (30” wide)
Not available
300 to 500 hp
590
72” (35” wide)
Not available
Variable Torque 208/240 Vac Altivar 58 TRX AC Drives
NEMA Type 1 and 1A 
(Gasketed)
NEMA Type 12
Motor Rated Horsepower
200 / 230 Vac
Maximum Continuous 
Output Current (A)
Space (Height)
Space (Height)
1 to 3 hp
11
12”
24”
5 hp
18
15”
24”
7.5 to 10 hp
31
24”
36”
15 to 25 hp
75
45”
45”
30 to 50 hp
143
72” (20” wide)
72” (20” wide)
Constant Torque 480 Vac Altivar 58 TRX AC Drives
NEMA Type 1 and 1A 
(Gasketed)
NEMA Type 12
Motor Rated Horsepower 
at 460 Vac
Maximum Continuous 
Output Current (A)
Space (Height)
Space (Height)
0.5 to 3 hp
5.8
12”
24”
5 to 7.5 hp
13
15”
24”
10 to 15 hp
24
24”
36”
20 hp
33
27”
36”
25 to 50 hp
66
45”
45”
50 to 75 hp
115
72” (20” wide)
72” (20” wide)
100 hp
124
72” (25” wide)
Not available
125 to 200 hp
240
72” (30” wide)
Not available
300 to 400
477
72” (35” wide)
Not available