Class 8998 Motor Control Centers
Space Requirements
216
09/2003
©
 2000–2003 Schneider Electric All Rights Reserved
Constant Torque 208/240 Vac Altivar 58 TRX AC Drives
NEMA Type 1 and 1A 
(Gasketed)
NEMA Type 12
Motor Rated Horsepower
200 / 230 Vac
Maximum Continuous 
Output Current (A)
Space (Height)
Space (Height)
1 to 3 hp
11
12”
24”
5 hp
18
15”
24”
7.5 to 10 hp
31
24”
36”
15 to 20 hp
60
45”
45”
25 to 40 hp
116
72” (20” wide)
72” (20” wide)
Variable Torque, Low Noise 480 Vac Altivar 58 TRX AC Drives
NEMA Type 1 and 1A 
(Gasketed)
NEMA Type 12
Motor Rated Horsepower
460 Vac
Maximum Continuous 
Output Current (A)
Space (Height)
Space (Height)
0.5 to 3 hp
5.8
12”
24”
5 to 7.5 hp
13
15”
24”
10 to 15 hp
24
24”
36”
20 hp
33
27”
36”
25 to 40 hp
52
45”
45”
50 to 75 hp
96
72” (20” wide)
72” (20” wide)
Variable Torque, Low Noise 208/240 Vac Altivar 58 TRX AC Drives
NEMA Type 1 and 1A 
(Gasketed)
NEMA Type 12
Motor Rated Horsepower
200 / 230 Vac
Maximum Continuous 
Output Current (A)
Space (Height)
Space (Height)
1 to 3 hp
11
12”
24”
5 hp
18
15”
24”
7.5 to 10 hp
31
24”
36”
15 to 20 hp
60
45”
45”
25 to 40 hp
116
72” (20” wide)
72” (20” wide)