Altivar
®
 
58 TRX AC Drives
Communication Parameters
©
 2000–2003 Schneider Electric All Rights Reserved
90
09/2003
W489
or 16#5FE8/28
USPL
0.01
Lower byte of machine speed
Value read
W490
or 16#5FE8/29
USPH
0.01
Upper byte of machine speed
Value read
W491
or 16#5FE8/2A
OPR
1%
Output power estimated by the 
drive controller
Value read
100% corresponds to nominal motor power
W492
or 16#5FE8/2B
AO1R
0.002 mA
Image of analog output AO1.
Write authorized if AO1 = No (not assigned): 
0 to 10000 (0 to 20 mA)
Read only if assigned: Value read
W493
or 16#5FE8/2C
UOP
0.1 V
Voltage applied to the motor. 
Exists only on Type FVC models.
Value read
W494
or 16#5FE8/2D
APH
1 kWh 
or
1 MWh
Drive power meter (kWh)
Value read. 
If bit 15 = 0, units are kWh as given by bits 0 to 14.
If bit 15 = 1, units are MWh as given by bits 0 to 14.
W495
or 16#5FE8/2E
RTH
1 hr
Total motor run time
Value read
Special DRIVECOM Registers
Word
Code
Units
Parameter Name and Description
Possible Values or Range
W600
or 16#603F
ERRD
ErrorCode
Fault code
Read/Write
16#0 = NOF: No fault 
16#1000 = CRF: Pre-charge relay fault
or = OLF: Motor overload (calculation or PTC probes)
or = SOF: Overspeed
16#2310 = OCF: Overcurrent (prolonged LIC)
16#2320 = SCF: Motor short-circuit (phase/earth)
16#3110 = OSF: Line supply overvoltage
16#3120 = USF: Line supply undervoltage (> 200 ms)
16#3130 = PHF: Line supply phase loss (> 1s)
16#3310 = OBF: DC bus overvoltage
or = OPF: Motor phase loss
16#4210 = OHF: Drive overheating (heatsink)
16#4310 = OTF: Motor overheating (PTC probes)
16#5520 = EEF: EEPROM memory fault
16#6100 = INF: Internal fault
16#6300 = CFF: Configuration incorrect (on initialization)
or = CFI: Configuration invalid (if writing a configuration)
16#7300 = ANF: Ramp not followed
or = LFF: Loss of 4–20 mA signal
or = TSF: Thermal sensor fault
16#7310 = SPF: Speed feedback missing or miswired
16#7510 = SLF: Serial link fault—keypad port (link break)
16#7520 = ILF: Fast serial link fault—options port (link break) 
or = CNF: Fast serial link communication network fault 
16#9000 = EPF: External fault
W601
or 16#6040
CMDD
Controlword
Command word—same as parameter CMD
Read/Write
W602
or 16#6041
ETAD
Statusword
Status word—same as parameter ETA
Write prohibited
W603
or 16#6042
LFRD
1 rpm 
[1]
SpeedSetP
Speed reference in rpm (reference not peak 
limited)
Read/Write
–32768 to 32767
W604
or 16#6043
FRHD
1 rpm
SpeedRef
Ramp output (signed) in rpm
Write prohibited
W605
or 16#6044
RFRD
1 rpm 
[1]
SpeedActV
Motor speed in rpm
Write prohibited
W606
or 16#6046/1
SMIL
1 rpm
SpdMinMax
Minimum speed in 32 bits
Equivalent to LSP (W251), but in rpm
Read/Write
0 to HSP
W607
SMIH
Reserved
0
W608
or 16#6046/2
SMAL
1 rpm
SpdMinMax
Maximum speed in 32 bits
Equivalent to HSP (W250), but in rpm
Read/Write
LSP to TFR
W609
SMAH
Reserved
0
[1]
For ATV58 Type FVC, if CMI Bit 9 = 0, units are in rpm; if CMI Bit 9 = 1, units are in 0.015 Hz.
Monitoring Registers (Continued)
Word
Code
Units
Description
Possible Values or Range