Check Optional Pumpout Compressor Water Piping 
If the optional storage tank and/or pumpout system are installed, check to ensure the 
pumpout condenser water has been piped in. Check for field-supplied shutoff valves and 
controls as specified in the job data. Check for refrigerant leaks on field-installed piping.
Check Relief Devices 
Be sure that relief devices have been piped to the outdoors in compliance with the latest 
edition of ANSI/ASHRAE Standard 15 and applicable local safety codes. Piping connections 
must allow for access to the valve mechanism for periodic inspection and leak testing. 
Relief valves are set to relieve at the 225 psig (1551 kPa) machine design pressure.
CAUTION
CAUTION
!
Water must be within design limits, clean, and treated to ensure proper machine 
performance and reduce the potential of tubing damage due to corrosion, scal-
ing, or erosion. Carrier assumes no responsibility for chiller damage resulting 
from untreated or improperly treated water.