Carrier 17/19EX Manual De Usuario

Descargar
Página de 437
If the readings on a field-installed starter are unsatisfactory, repeat the test at the motor with 
the power leads disconnected. Satisfactory readings in this second test indicate the fault is 
in the power leads. 
Note: Unit-mounted starters do not have to be megohm tested.
Check Insulation Resistance (Open-Drive Motor)
Before operating voltages is applied to the motor, whether for checking rotation direction or 
for actual operation, the resistance of the stator winding insulation should be measured.
The test voltage, based on the motor operating voltage, is as follows:
This is particularly important if the motor may have been exposed to excessive dampness 
either during transit or while in storage. A ‘‘megger’’ type instrument can be used to measure 
the insulation resistance. The test voltage should be applied between the entire winding (all 
winding leads connected together) and ground for approximately one minute with the winding at 
ambient temperature. The recommended minimum insulation resistance is determined as 
follows:
Operating Voltage
DC Test Voltage
 0-    900
500
 901-  7000
1000
7001-14500
2500