Carrier 17/19EX Manual De Usuario

Descargar
Página de 437
Oil Charge 
If oil is added, it must meet Carrier’s specification for centrifugal compressor usage as 
described in the Scheduled Maintenance, 
 section. 
On hermetic machines, add oil through the oil drain charging valve (
Item 26). A 
pump is required for adding oil against refrigerant pressure. The pumping device must be able 
to lift from 0 to 150 psig (0 to 1034 kPa) or above unit pressure. On open-drive machines, oil 
may be added through the oil drain and charging valve (
, Item 18) using a pump. 
However, an oil charging elbow on the seal-oil return chamber (
) allows oil to be added 
without pumping. The seal oil return pump automatically transfers the oil to the main oil 
reservoir. 
Oil should only be charged or removed when the machine is shut down. Maximum oil level is 
the middle of the upper sight glass.
Power Up the Controls and Check the Oil Heater 
Ensure that an oil level is visible in the compressor before energizing controls. A separate 
disconnect energizes the oil heater and the control circuit. When first powered, the LID should 
display the default screen within a short period of time. 
The oil heater is energized by powering the control circuit. This should be done several hours 
before start-up to minimize oil-refrigerant migration. The oil heater is controlled by the PIC and 
is powered through a contactor in the power panel. Starters contain a separate circuit breaker to