the refrigerant charging valve, (
 and 
) or to the pumpout charging connection. 
First evacuate the nitrogen holding charge from the vessels. Charge the refrigerant as a gas 
until the system pressure exceeds 35 psig (141 kPa). After the machine is beyond this pressure 
the refrigerant should be charged as a liquid until all of the recommended refrigerant charge has 
been added.
Trimming Refrigerant Charge
The 17/19EX is shipped with the correct charge for the design duty of the machine. Trimming 
the charge can be best accomplished when design load is available. To trim, check the 
temperature difference between leaving chilled water temperature and cooler refrigerant 
temperature at full load design conditions. If necessary, add or remove refrigerant to bring the 
temperature difference to design conditions or a minimum differential.