alert threshold (18 psid [124 kPa]). Once running, the auxiliary oil pump will remain on until the 
compressor is turned off and will deenergize with the main oil pump after the post-lube time 
period.
Shaft Seal Oil Control (Open Drive Machines Only)
All open drive machines require that the shaft seal be bathed in oil at all times, especially 
when the machine is not running. This ensures that refrigerant does not leak past the seal. The 
PIC control will energize the oil pump for one minute if the oil pump has not operated during the 
past 12 hours. 
It is important to note that if control power is to be turned off for longer than this period, the 
refrigerant charge must be pumped over into the utility vessel. Because the oil heater will also 
be off during this time, storing the refrigerant will also prevent refrigerant migration into the oil.
Ramp Loading Control 
The ramp loading control slows down the rate at which the compressor loads up. This control 
can prevent the compressor from loading up during the short period of time when the machine 
is started, and the chilled water loop has to be brought down to normal design conditions. This 
helps reduce electrical demand charges by slowly bringing the chilled water to control point. 
However, the total power draw during this period remains almost unchanged.