There are 2 methods of ramp loading with the PIC. Ramp loading can be based on chilled 
water temperature or on motor load. 
1. Temperature ramp loading limits the rate at which either leaving chilled water or entering 
chilled water temperature decreases by an operator-configured rate. The lowest 
temperature ramp table will be used the first time the machine is started (at 
commissioning). The lowest temperature ramp rate will also be used if machine power has 
been off for 3 hours or more (even if the motor ramp load is selected). 
2. Motor load ramp loading limits the rate at which the compressor motor current or 
compressor motor load increases by an operator-configured rate. 
The 
TEMP (Temperature) PULLDOWN, LOAD PULL DOWN, and SELECT RAMP TYPE 
may be viewed/modified on the LID Equipment Configuration table, Config table (see 
). 
Motor load is the default type.
Capacity Override (See 
These can prevent some safety shutdowns caused by exceeding motor amperage limit, 
refrigerant low temperature safety limit, motor high temperature safety limit, and condenser high 
pressure limit. In all cases there are 2 stages of compressor vane control. 
1. The vanes are held from opening further, and the status line on the LID indicates the reason 
for the override. 
2. The vanes are closed until condition decreases below the first step set point, and then the 
vanes are released to normal capacity control.